Outback Power Systems OBX-IC2024S-120/60 Battery Charger User Manual


 
29
STATUS/FX/PAGE2-------------------
choose category:
PG1 ERROR WARN PG3
ERROR Screens
Allscreensreadstatusas“No”undernormalconditions.Iftheunitshutsoduetoaspeciederrorcondition,that
screenwillchangeto“Yes”.
• low ac output voltage: load too high; Inverter could not supply enough AC voltage to meet demand
• stacking error detected: communication problem among stacked units
• inverter overtemp: Inverter has reached its maximum allowed operating temperature
• low battery voltage: battery voltage is below the LOW BATTERY CUT-OUT VOLTAGE set point
(This error can be triggered by other events. It can trigger with low AC output or AC shorted.)
• phase loss error: not active in
the OBX-IC2024S-120/60 Inverter
• highbatteryvoltage:batteryvoltageroseabovethesafehighbatteryvoltagelevelfor10seconds
• ac output shorted: Inverter reached its maximum current and shut down
• ac output backfeed: usually indicates another AC power source was connected to the Inverter’s AC output
These are hard faults. The Inverter must be turned o and then on to reset. ERROR screens can only display errors;
they do not oer any means to correct them. Generally the nature of the error suggests how to correct it.
STATUS/FX/PAGE1-------------------
choose category:
MODES METER BATT PG2
Pressing the <PG2> soft key brings
up more STATUS categories.
Pressing the <ERROR> soft key
brings up the rst ERROR screen.
Pressing the <DOWN> soft key
brings up successive METER screens.
Status Error Screens
STATUS/FX/ERROR-----------P00
low ac output No
voltage
DOWN STATUS PORT
STATUS/FX/ERROR----------P00
stacking No
error detected
DOWN UP TOP PORT
STATUS/FX/ERROR----------P00
low battery No
voltage
DOWN UP TOP PORT
STATUS/FX/ERROR----------P00
inverter No
overtemp
DOWN UP TOP PORT
STATUS/FX/ERROR----------P00
phase loss No
error
DOWN UP TOP PORT
STATUS/FX/ERROR----------P00
ac output No
shorted
DOWN UP TOP PORT
STATUS/FX/ERROR----------P00
high battery No
voltage
DOWN UP TOP PORT
STATUS/FX/ERROR----------P00
ac output
backfeed
DOWN UP TOP PORT
STATUS/FX/ERROR------------------
end of error menu
UP TOP STATUS
Push <STATUS> to
return to the “choose
category”
STATUS /
FX/PAGE2
screen.
Push <TOP> to
return to the rst
ERROR screen.