Outback Power Systems OBX-IC2024S-120/60 Battery Charger User Manual


 
33
INSTALLATION CHECK LIST
ITEM YES NO
Manual read and reviewed?
System mounted with the recommended number and sized fasteners?
System installed according to required codes and regulations?
System inspected?
System grounded?
Inverter output
connected to load circuit with 30 AC amp maximum overcurrent protection?
Inverter AC sources protected with 30 AC amp maximum overcurrent protection?
Pertheinstructionsregardingneutralandgroundinstallationonpage7,
If the installation is non-bonded,
Inverter green/yellow wire connected?
Input and output neutral wires isolated from each other?
Generator’s neutral and ground bonded together?
OR
If the installation is bonded,
Inverter green/yellow wire disconnected?
Input and output neutral wires on a common bus?
Generator’s neutral and ground isolated from each other?
All cables torqued to OutBack specications?
Batteryconnectionsto10foot-lbs/13.55Nm?
InverterDCterminalsto5foot-lbs/5.8Nm?
Inverter DC terminals and all exposed conductors coated in dielectric grease?