STATUS/FX/DISCON-----------P00
acin freq No
too high
DOWN STATUS PORT
STATUS/FX/DISCON-----------P00
acin voltage No
> max
DOWN UP TOP PORT
STATUS/FX/DISCON----------P00
acin freq No
too low
DOWN UP TOP PORT
STATUS/FX/DISCON-----------P00
acin voltage No
< min
DOWN UP TOP PORT
STATUS/FX/PAGE2----------------
choose category:
PG2 DISCON SELL MAIN
STATUS/FX/DISCON----------------
end of DISCON menu
UP TOP STATUS
DISCON(NECT) Screens
• acin freq too high:
displays“Yes”iftheACsourceexceeds66HzandtheInverterdisconnectsfromthesource
• acin freq too low:displays“Yes”iftheInverterdisconnectsfromanACsourcebelow54Hz
• acin voltage > max: the source of the AC voltage exceeds the Inverter maximum of 140 Vac
• acin voltage < min:thesourceoftheACvoltagefallsbelowtheInverterminimumof108Vac
STATUS/FX/PAGE2-----------------
choose category:
PG2 DISCON SELL MAIN
STATUS/FX/PAGE2------------------
choose category:
PG1 ERROR WARN PG3
WARN(ING) Screens
Allwarningscreensreadstatusas“No”undernormalconditions.Iftheappropriateconditionismet,thatscreenwill
changeto“Yes.”
acin freq too high:• AC source is above 66 Hz (upper limit) and will be dropped
acin freq too low:• ACsourceisunder54Hz(lowerlimit)andwillbedropped
acin voltage too high• : AC source’s voltage is over 140 Vac (default limit) and will be dropped
acin voltage too low: • ACsource’svoltageisunder108Vac(defaultlimit)andwillbedropped
acin input current exceeds max: • AC loads are drawing more current than the rating of the FX allows
temperature sensor fault: • an internal FX temperature sensor is malfunctioning
internal comm error detected:• there is a communication problem between MATE and Inverter (see p. 23)
internal fan failure detected: • the Inverter’s internal cooling fan is not operating properly
The following items are not warnings, but are data readings related to the temp sensor warning
• airtemp: displays a numeric value representing the air temperature around the Inverter
• fettemp: displays a numeric value representing the temperature of the FETs (Field Eect Transistors)
• captemp: displays a numeric value representing the temperature of the ripple capacitors
(These values are used for troubleshooting purposes. The higher the numerical value, the cooler the temperature.)
Status Discon(nect) Screens
Pressing the <PG3> soft key brings
up more STATUS categories.
Pressing the <DISCON> soft key
brings up the rst DISCON screen.
Pressing the <DOWN> soft key brings up
successive DISCON screens.
Push <STATUS> to return
tothe“choosecategory”
STATUS /FX/PAGE2 screen.
Push <TOP> to
return to the rst
ERROR screen.
Push <MAIN> to
return to the Main
screen.