MDS-D2/DH2 Series Instruction Manual
1.4 Installation of the Drive Unit
(2) Heat radiation countermeasures outside the control panel
Measure the temperature at 40mm form tops of all units, and design the temperature rise so that it is 20°C or less
against the ambient temperature.
If the temperature rise at the temperature measurement position exceeds 20°C, consider adding a fan.
POINT
The temperature of some units may rise locally, because air accumulates at a particular point. Therefore, take a
temperature measurement in each unit.
If a temperature at even one point exceeds 20°C in the temperature measurements, take a heat radiation countermeasure
such as addicting fans.
40mm
40mm
Temperature measurement position
Side face Back face