Error codes can take three forms:
•Alarm
: alerts you to the alarm cause and shuts
down the pump.
Deviation
: alerts you to the problem, but pump
may continue to run past the set limits until the
system’s absolute limits are reached.
Advisory: information only. Pump will continue to
operate.
NOTE: On A
dvanced motors, flow (K codes) and
pressure
(P codes) can be designated as alarms or
deviatio
ns. See Setup Screen 4, page 20.
NOTE: In the error codes listed below, an “X” means
the code is associated with the display only.
NOTE: In the e
rror codes listed below, a “_” in the
code is a plac
eholder for the number of the pump
where the eve
nt occurred.
NOTE: The blink code is displayed using the power
indicator on the motor. The blink code given below
indicates the sequence. For example, blink code 1–2
indicates 1 blink, then 2 blinks; the sequence then
repeats.
NOTE: A blink code of 9 is not an error code, but an
indicator of which pump is active (
softkey has
been pushed, see RunScreen1,page12).
Display
Code
Applicable
Motor
Blink
Code
Alarm or
Deviation
Description
None Basic 6 Alarm
The Mode Select knob is set between Pressure
and
Flow
. Set knob to the desired mode.
None Basic and
Advanced
9 None
A blink code of 9 is not an error code, but an indicator of
which pump is active.
CAC_
Advanced None Alarm
Display detects a loss of CAN communication. Flashing
alarm appears on the display, and the blink code occurs.
CAD_
Advanced 2–3 Alarm
Unit detects a loss of CAN communication. This alarm is only
logged. No flashing alarm appears on the display, but the
blinkcodedoesoccur.
CAG_
Advanced 2–4 Alarm
Display detects a loss of modbus communication when
control access is set to modbus.
CCN_
Basic and
Advanced
3–6 Alarm
Circuit board communication failure.
K1D_
Advanced 1–2 Alarm Flow is below minimum limit.
K2D_
Advanced None Deviation Flow is below minimum limit.
K3D_
Advanced None Deviation Flow exceeds maximum target; also indicates pump runaway
condition exists.
K4D_
Basic and
Advanced
1 Alarm Flow exceeds maximum target; also indicates pump runaway
condition exists.