Honeywell NXL Welding System User Manual


 
30(96) Cabling and connections Honeywell
HoneywellHoneywell
Honeywell
6
6.1.1.1 Cable and fuse sizes
Terminal cable size (min/max) Frame Type I
L
[A]
Fuse
[A]
Mains
cable
Cu [mm
2
]
Main terminal
[mm
2
]
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
Relay
terminal
[mm
2
]
MF2 NXL0002 2 10 2*1.5+1.5 0.5—2.5 0.5—2.5 0.5—1.5 0.5—2.5
MF3 NXL0003—0006 3-6 16 2*2.5+2.5 0.5—2.5 0.5—2.5 0.5—1.5 0.5—2.5
Table 6-2. Cable and fuse sizes for NXL Compact, 208 - 240V
Terminal cable size (min/max) Frame Type I
L
[A]
Fuse
[A]
Mains
cable
Cu [mm
2
]
Main terminal
[mm
2
]
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
Relay
terminal
[mm
2
]
MF2 NXL0001—0002 1-2 10 3*1.5+1.5 0.5—2.5 0.5—2.5 0.5—1.5 0.5—2.5
MF3 NXL0003—0005 1-5 10 3*1.5+1.5 0.5—2.5 0.5—2.5 0.5—1.5 0.5—2.5
MF4 HVAC03—09 7—9 10 3*1.5+1.5 1—4 1—2.5 0.5—1.5 0.5—2.5
MF4 HVAC12 12 16 3*2.5+2.5 1—4 1—2.5 0.5—1.5 0.5—2.5
MF5 HVAC16 16 20 3*4+4 1—10 1—10 0.5—1.5 0.5—2.5
MF5 HVAC23 22 25 3*6+6 1—10 1—10 0.5—1.5 0.5—2.5
MF5 HVAC31 31 35 3*10+10 1—10 1—10 0.5—1.5 0.5—2.5
MF6 HVAC38—45 38-
45
50 3*10+10 2.5—50 Cu
6—50 Al
6—35 0.5—1.5 0.5—2.5
MF6 HVAC61 61 63 3*16+16 2.5—50 Cu
6—50 Al
6—35 0.5—1.5 0.5—2.5
Table 6-3. Cable and fuse sizes for NXL, 380 – 500V
Note! This cable recommendation is based on standard EN 60204-1 and PVC isolated cable where there
is either one cable on a shelf in temperature of + 40°C or four cables on a shelf in temperature of + 30°C.