7.4.8.5 Fieldbus parameters
RS-485 communication status (I6.10.1)
With this function you can check the status of the RS 485 bus. If the bus is not in use, this value is 0.
xx.yyy
xx = 0 – 64 (Number of messages containing errors)
yyy = 0 – 999 (Number of messages received correctly)
Fieldbus protocol (P6.10.2)
With this function you can select the fieldbus communications protocol.
0 = Not used
1 = Modbus protocol
Slave address (P6.10.3)
Set here the slave address for the Modbus protocol. You can set any address between 1 and 255.
Baud rate (P6.10.4)
Selects the baud rate used with the Modbus communication.
0 = 300 baud
1 = 600 baud
2 = 1200 baud
3 = 2400 baud
4 = 4800 baud
5 = 9600 baud
6 = 19200 baud
7 = 38400 baud
8 = 57600 baud
Stop bits (P6.10.5)
Set the number of stop bits used in Modbus communication
0 = 1 stop bit
1 = 2 stop bits
Parity type (P6.10.6)
Here you can select the type of parity checking used with the Modbus communication.
0 = None
1 = Odd
2 = Even