4.3 Connection of Operation Panel I/O Unit
93
4.3.3 Connecting with Manual Pulse Generator (MPG)
Both 5V power supply type (UFO-01-2Z9) and 12V power supply type (HD60C) manual pulse generator can be used.
Take the maximum cable length, etc. into consideration when selecting.
(Note) Set one of the following parameters which is suitable for your manual pulse generator.
- 5V manual pulse generator (UFO-01-2Z9) : #1240 set12/bit0 = 1 (100 pulse/rev)
-12V manual pulse generator (HD60C) : #1240 set12/bit0 = 0 ( 25 pulse/rev)
(1) Connecting with 5V manual pulse generator (maximum cable length: 20m)
Connect the 5V manual pulse generator to the connector MPG.
(2) Connecting with 12V manual pulse generator (maximum cable length: 50m)
Connect the 12V manual pulse generator to the connector MPG.
(Note 1) When selecting a manual pulse generator, make sure that its case and 0V terminal are insulated.
(Note 2) Select 25pulse/rev or 100pulse/rev on the parameter screen.