Xantrex Technology DR2424 Battery Charger User Manual


 
Front Panel Controls and Indicators
975-0012-01-02 Rev A 3–11
Figure 3-7
ODP Enabled/Disabled Positions
Important:
Most AC appliances will operate properly with an AC pass-through
voltage between 95 and 105 volts. Setting the AC Transfer Voltage potentiometer between
these values will allow the incoming source voltage to drop to this level and still operate
the connected appliances (load). If the appliances do not operate properly at the lower AC
utility pass-through voltage, increasing the setting of the potentiometer (toward MAX)
allows the inverter to transfer to battery power (providing full AC output) during these
periods.
Important:
When setting the AC Transfer Voltage potentiometer for generator
applications, the setting may need to be lowered if high powered loads cause the generator
voltage to momentarily drop.
AC Transfer Voltage (Adjustable)
with ODP Enabled
AC Transfer Voltage (Adjustable)
with ODP Disabled
Maximum
(105 Vac for 120 Vac models)
Maximum
(105 Vac for 120 Vac models)
Minimum
(45 Vac for 120 Vac models)
Minimum
(45 Vac for 120 Vac models)
Figure 3-8
Typical Setting for Most Utility Application
Typical Setting Range for Utility
Application (ODP OFF)
Typical Setting Range for Utility
Application (ODP ON)