PARAMETERS
108
4.2.38 V/F control frequency (voltage) (Pr. 100 to Pr. 109)
Pr. 100 "V/F1 (first frequency)"
Pr. 101 "V/F1 (first frequency voltage)"
Pr. 102 "V/F2 (second frequency)"
Pr. 103 "V/F2 (second frequency voltage)"
Pr. 104 "V/F3 (third frequency)"
Pr. 105 "V/F3 (third frequency voltage)"
Pr. 106 "V/F4 (fourth frequency)"
Pr. 107 "V/F4 (fourth frequency voltage)"
Pr. 108 "V/F5 (fifth frequency)"
Pr. 109 "V/F5 (fifth frequency voltage)"
You can make a dedicated V/F pattern by using V/F (frequency Voltage/Frequency) control to set V/F
characteristics from the start to the basic frequency and basic voltage as desired.
#
Desired V/F characteristics can be set by presetting V/F1 (first frequency voltage/first frequency), V/F2,
V/F3, V/F4 and V/F5 in the corresponding parameters.
Parameter
Number
Factory
Setting
Setting Range Remarks
100 9999 0 to 120Hz, 9999
101 0 0 to 1000V
102 9999 0 to 120Hz, 9999
103 0 0 to 1000V
104 9999 0 to 120Hz, 9999
105 0 0 to 1000V
106 9999 0 to 120Hz, 9999
107 0 0 to 1000V
108 9999 0 to 120Hz, 9999
109 0 0 to 1000V
Set "2" in Pr. 71 and a value
other than 9999 in Pr. 19.
These functions are active
only when Pr. 60 = 0.
0
V/F5
V/F4
V/F3
V/F2
V/F1
Voltage
Base frequency voltage
(Pr. 19)
Boost value
(Pr. 0)
V/F characteristic
Base frequency
(Pr. 3)
Frequency
<Setting>
(1) Confirm the settings of Pr. 19, Pr. 60 and Pr. 71.
Parameter Number Description
19
Set the rated motor voltage.
This function is not activated if its value is "9999" and "8888" (factory setting).
60 Set "0" (ordinary operation mode).
71 Set "2" (V/F 5-point flexible characteristic).
Pr. 19 "base frequency voltage"
Pr. 47 "second V/F (base frequency)"
Pr. 60 "intelligent mode selection"
Pr. 71 "applied motor"
Related parameters