OPERATION/CONTROL
51
3.2.8 Copy mode
By using the operation panel (FR-DU04), the parameter values can be copied to another inverter (only the
FR-F500 series).
1) Operation procedure
After reading the parameter values from the copy source inverter, connect the operation panel to the copy
destination inverter, and write the parameter values.
After writing the parameters to the inverter of copy destination, always reset the inverter, e.g. switch power
off once, before starting operation.
SET SET SET
SET
Connect to copy destination inverter.
#
Parameter setting mode
(Note 1)
(Note 1)
(Note 1)
#
Parameter read
#
Parameter write
#
Parameter verify
Press for
1.5 s.
Press for
1.5 s.
Press for
1.5 s.
FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
After writing the parameters,
always reset the inverter before
operation.
Note: 1. While the copy function is being activated, the monitor display flickers. The display returns to the
lit-up state on completion of the copy function.
2. If a read error occurs during parameter read, "read error (E.rE1)" is displayed.
3. If a write error occurs during parameter write, "write error (E.rE2)" is displayed.
4. If a data discrepancy occurs during parameter verify, the corresponding parameter number and
"verify error (E.rE3)" are displayed alternately. If the direct frequency setting or jog frequency
setting is discrepant, "verify error (E.rE3)" flickers. To ignore this display and continue verify,
press the
SET
key.
5. When the copy destination inverter is not the FR-F500 series, "model error (E.rE4)" is displayed.
Reference
: It is recommended to read the parameter values after completion of parameter setting.
By writing the parameter values from the operation panel fitted to a new inverter after inverter
replacement, parameter setup can be completed.