Mitsumi electronic 55K Welding System User Manual


 
INSTALLATION AND WIRING
24
2.2.5 Connection of stand-alone option units
The inverter accepts a variety of stand-alone option units as required.
Incorrect connection will cause inverter damage or accident. Connect and operate the option unit carefully in
accordance with the corresponding option unit manual.
(
1
)
Connection of the FR-BU brake unit (option)
Connect the optional FR-BU brake unit as shown below to improve the braking capability during deceleration.
MC
R
L
1
S
L
2
T
L
3
U
V
W
+
P
N
IM
PR
P/+
N/-
HA
HB
HC
Brake unit
FR-BU-(H)
Resistor unit
FR-BR-(H)
THS
TH2
TH1
PPR
ON
MC
OFF
MC
Inverter
Motor
T (Note 4)
Note: 1. Connect the inverter terminals (P, N)
〈+
,
−〉
and FR-BU brake unit terminals so that their terminal
signals match with each other. (Incorrect connection will damage the inverter.)
2. The wiring distance between the inverter, brake unit and resistor unit should be within 5m
(16.40feet). If twisted wires are used, the distance should be within 10m (32.81feet).
3. When the transistor in the brake unit fails, the brake transistor bacomes extremely hot and it has
a chance to get fire. Therefore, install a magnetic contactor on the inverter's power supply side to
shut off a current in case of failure.
4. For the power supply of 400V class, install a voltage-reducing transformer.
2