Mitsumi electronic 55K Welding System User Manual


 
PARAMETERS
73
4.2.8 Starting frequency (Pr. 13)
Pr. 13 "starting frequency"
You can set the starting frequency between 0 and 60Hz.
#
Set the starting frequency at which the start signal is switched on.
Parameter
Number
Factory Setting Setting Range
13 0.5Hz 0 to 60Hz
60
Pr.13
ON
0
Forward
rotation
Output frequency
(Hz)
Setting range
Frequency setting signal (V)
Time
Note: The inverter will not start if the frequency setting signal is less than the value set in Pr. 13 "starting
frequency".
For example, when 5Hz is set in Pr. 13, the motor will start running when the frequency setting signal
reaches 5Hz.
CAUTION
Note that when the Pr. 13 setting is less than the Pr. 2 value, merely turning on the
start signal will start the motor running at the set frequency if the command frequency
is not input.
4
Pr. 2 "minimum frequency"
Related parameters