APC 412 kVA Battery Charger User Manual


 
CHAPTER 5: SPECIFICATIONS
31
Technical Reference
This section contains operation, input, output, physical, and compliance specifications for the UPS.
Operational Specifications
System Power Array with hot-swappable modules that are redundant, scalable,
self-diagnosing, and fault-tolerant
Topology On-line, double conversion with input power factor correction
Power Capacity 4 –16 kVA N, 12 kVA N+1
Battery Type Hot-swappable, sealed, maintenance-free, lead acid, 3 – 5 years life
Battery Charger Automatic float, equalized high frequency PWM charger
Battery Recharge Time < 4 hours with standard supplied packs in the frame
Extended Battery Option Yes
Ambient Temperature
0 – 40 °C
Relative Humidity < 95% non-condensing
Elevation 0 – 10,000 ft (3,000 mm)
Input Specifications
Nominal Input Voltage 200, 208, 220, 230, 240 Vac; 60 or 50 Hz, 1 phase, 3 wire
Input Voltage Range 155 to 276 Vac with batteries charging & supporting full load
Input Frequency Range 47 – 63 Hz
Input Power Factor Approximately. 0.98 @ full load
Input Current THD Approximately. 6% @ full load
Input Inrush Current Maximum 150% of full load current
Input Generator Sizing 1.5 x UPS capacity