APC 412 kVA Battery Charger User Manual


 
CHAPTER 4: MESSAGES
19
PowerView Message Meaning Corrective Action
Redundancy Restored. Power module redundancy loss occurred
and was restored. Either additional
modules have been installed or the load
has been reduced.
Load is No Longer above
Alarm Threshold.
The load exceeded the load alarm
threshold. The situation has been
corrected because either the load
decreased or the threshold was
increased.
General
Status
(continued)
Min Runtime restored. The system runtime dropped below the
configured minimum runtime and was
restored.
Either additional battery modules were
installed, the existing battery modules
were recharged, the load was reduced,
or the threshold was raised.
No corrective action necessary.
Bad Battery Module. A battery module failed and requires
replacement.
Bad Power Module. A power module failed and requires
replacement.
Intelligence Module is
installed and failed.
The MIM failed and requires
replacement.
Module
Failure
Redundant Intelligence
Module is installed and
failed.
The RIM failed and requires
replacement.
Refer to module replacement
procedure S
YMMETRA RM
I
NSTALLATION MANUAL.
Load is above kVA alarm
threshold.
The load has exceeded the user
specified load alarm threshold.
Option 1: Reduce the load.
Option 2: Use the PowerView
interface to raise the alarm
threshold.
Threshold
Alarm
Redundancy has been
lost.
The UPS no longer detects redundant
power modules. Either power module(s)
failed or the load increased.
Option 1: If possible, install
additional power modules.
Option 2: Decrease the load.
Option 3: Disable the
redundancy alarm by setting
redundancy to zero.
(Startup>Setup>Alarms>
Redundancy>Zero)