APC 412 kVA Battery Charger User Manual


 
CHAPTER 3: MENU COMMANDS
16
Setup Menu (continued)
Menu Item Function Options
Alarms Sets the alarm thresholds. None
Redundancy
An audible alarm sounds if the redundancy falls below
this level.
0(default), 1, or 2
Load
An audible alarm sounds when the load exceeds this
limit. (Upper value is limited by the maximum power of
the UPS.)
Never(default), 1, 2, 3, 4,
5, 6, 7, 8, 9, 10, or 12 kVA
Runtime
An audible alarm sounds if the available runtime falls
below this level (Hours:min).
0:0(default),5m, 10m,
15m, 30m, 45m,1h, 2h, 3h,
4h, 5h, 6h, 7h, or 8h
Bypass
In the unlikely event that both the UPS fails and the input
voltage or line frequency is outside of normal range, this
option lets you choose to go into Bypass mode or drop
the load.
Go to Bypass or
Drop Load
Copy Not used with this UPS. None
Other Remaining user-defined settings. None
Self Test
The UPS can automatically test itself at this user-
specified interval.
At Power On, 7 days,
14 days(default) , or
Disabled
UPS ID Assigns an eight-character text string to a system.
Output
Sets output voltage. Selection depends upon system
configuration.
200V, 208V, 220V, 230V,
or 240V
Vout Reporting Reports the most significant output voltage. Auto