PowerView Message Meaning Corrective Action
AC adequate for UPS but
not for bypass.
The UPS will function on-line with the
input voltage, but in the event that
bypass is required, the input voltage is
not adequate to power the load
equipment.
Option 1: Improve the incoming
voltage.
Option 2: Proceed with startup.
Normal bypass is not available.
Start-Up
(continued)
Low/No AC input, startup
on battery.
Input voltage is not adequate to start the
UPS. If startup proceeds, the UPS will
function from battery.
Option 1: Abort startup until
acceptable input voltage is
present.
Option 2: Proceed with startup.
Battery will be discharged.
# of batteries increased. At least one battery module has been
added to the system.
# of batteries decreased. At least one battery has been removed
from the system.
# of Pwr Modules
increased.
At least one power module has been
added from the system.
Intelligence Module
inserted.
A MIM has been installed into the UPS.
Intelligence Module
removed.
A MIM has been removed from the UPS.
Redundant Intelligence
Module inserted.
A RIM has been installed into the UPS.
Redundant Intelligence
Module removed.
A RIM has been removed from the UPS.
# of External Battery
Cabinets increased.
At least one external battery cabinet has
been connected to the frame.
General
Status
# of External Battery
Cabinets decreased.
At least one external battery cabinet has
been disconnected from the UPS.
No corrective action necessary.