CHAPTER 2: GETTING STARTED
6
Bypass Operation
In addition to the automatic bypass, a maintenance bypass switch is provided with the UPS. Placing this switch in
bypass mode connects the load equipment to the branch circuit, even if the UPS is turned OFF.
When using the maintenance bypass, the input circuit breaker must be ON, or power will not be
supplied to the Load screen.
Follow the steps below to connect directly to the branch circuit (mains) via the automatic bypass.
>Control Logging
Status Display
Setup Diags
Accessories Help
>Turn Load Off
Do Self Test
Simulate Power Fail
Graceful Reboot ➪
Graceful Turn Off
Start Runtime Cal
>UPS into Bypass
Confirm:
UPS into Bypass
NO, ABORT
>YES,UPS into Bypass
UPS LOAD IS BYPASSED
Press any key...
1. Use ‘ESC’ to view to Main Menu , and then
select
CONTROL.
2. Select the
UPS INTO BYPASS command.
3. Confirm choice by selecting YES .
4. You will see message . In addition, the green
LOAD ON and yellow BYPASS status indicators will