APC 412 kVA Battery Charger User Manual


 
CHAPTER 4: MESSAGES
22
PowerView Message Meaning Corrective Action
Input circuit breaker
tripped open.
The input circuit breaker on the UPS
tripped open. Input voltage is
disconnected to the UPS.
Option 1: If this occurs in
conjunction with an overload
condition, decrease the load and
reset the breaker.
Option 2: If no overload
condition exists, reset breaker. If
it trips open again, call your
contract service provider or APC
Technical Support.
System level fan failed. A cooling fan in the UPS frame failed. Call your contract service
provider or APC Technical
Support.
The Redundant
Intelligence Module (RIM)
is in control.
The MIM failed, and the RIM is
functioning as the primary intelligence
module.
Replace the intelligence module.
Refer to module replacement
procedure.
General Fault
(continued)
IIC inter-module
communications failed.
The communications between the MIM
and at least one other module failed.
Call your contract service
provider or APC Technical
Support.