3. Implementation of the communication option cards
Option card fault
The [internal com. link] (ILF-) fault appears when the following serious problems occur:
- Hardware fault on the option card
- Dialog fault between the option card and the drive
The
[Internal link fault 1] (ILF1) diagnostic parameter can be used to obtain more detailed information about the origin of the last
[internal com. link] (ILF) fault:
This parameter can be accessed on the graphic display terminal only, in the
[1.10 DIAGNOSTICS] (DGt-) menu, [MORE FAULT
INFO]
(AFI-).
When the External Fault function is used via a communication card, the Altivar 38 would display EPF, but the Altivar 61 now displays
EPF2.
When the Fast Stop function is used via a communication card, the Altivar 38 would display RDY, but the Altivar 61 now displays FST.
It is essential to follow the Altivar 38 internal variables manual when the Altivar 61 is being used in 8 serie mode. If not, migration may
not proceed smoothly.
Value Description of parameter values Value Description of parameter values
0 No fault 8 Faulty analog input
1 Loss of internal communication with the drive 9 Faulty analog output
2 Hardware fault detected 10 Faulty logic input
3 Error in the EEPROM checksum 11 Faulty logic output
4 Faulty EEPROM 101 Unknown card
5 Faulty Flash memory 102 Exchange problem on the drive internal bus
6 Faulty RAM memory 103 Time out on the drive internal bus (500 ms)
7 Faulty NVRAM memory