3. Implementation of the communication option cards
Option card fault
The [internal com. link] (ILF-) fault appears when the following serious problems occur:
- Hardware fault on the option card
- Dialog fault between the option card and the drive
The
[Internal link fault 1] (ILF1) diagnostic parameter can be used to obtain more detailed information about the origin of the last
[internal com. link] (ILF) fault:
This parameter can be accessed on the graphic display terminal only, in the
[1.10 DIAGNOSTICS] (DGt-) menu, [MORE FAULT
INFO]
(AFI-).
• When the External Fault function is used via a communication card, the Altivar 38 would display EPF, but the Altivar 61 now displays
EPF2.
• When the Fast Stop function is used via a communication card, the Altivar 38 would display RDY, but the Altivar 61 now displays FST.
• It is essential to follow the Altivar 38 internal variables manual when the Altivar 61 is being used in 8 serie mode. If not, migration may
not proceed smoothly.
Value Description of parameter values Value Description of parameter values
0 No fault 8 Faulty analog input
1 Loss of internal communication with the drive 9 Faulty analog output
2 Hardware fault detected 10 Faulty logic input
3 Error in the EEPROM checksum 11 Faulty logic output
4 Faulty EEPROM 101 Unknown card
5 Faulty Flash memory 102 Exchange problem on the drive internal bus
6 Faulty RAM memory 103 Time out on the drive internal bus (500 ms)
7 Faulty NVRAM memory