3. Implementation of the communication option cards
3. 8. Communication via Modbus Plus network
3. 8. 1. Reminder of the possible connection methods: Same as existing
3. 8. 2. Configuring the drive address on the Modbus Plus network
On the Altivar 38’s Modbus Plus option card, the drive address is coded using switches 1 to 6 (LSB to MSB).
Therefore, simply transfer the switch configuration of a Modbus Plus option card for Altivar 38 to the switches of a Modbus Plus option card
for Altivar 61.
The address corresponds to the binary number given by position 0 or 1 of the 6 switches increased by 1.
E.g., address 6 = 5 (+1)
3. 8. 3. Configuring the drive in "ATV38 Interchangeability" mode
In order to use the Altivar 38 Peer Cop and Global Data variables rather than those of the Altivar 61, you need to set the right-hand switch
to the ON position and restart the drive.
Switch 0 (OFF): Altivar 61 mode
Switch 1 (ON): 8 serie mode
1 = GND
2 = Tx
3 = Rx
ATV38 ATV61
Address Switches Address Switches Address Switches Address Switches
1234 5678 1234 5678 1234 5678 1234 5678
1 0000 0000 17 0000 1000 33 0000 0100 49 0000 1100
2 1000 0000 18 1000 1000 34 1000 0100 50 1000 1100
3 0100 0000 19 0100 1000 35 0100 0100 51 0100 1100
4 1100 0000 20 1100 1000 36 1100 0100 52 1100 1100
5 0010 0000 21 0010 1000 37 0010 0100 53 0010 1100
6 1010 0000 22 1010 1000 38 1010 0100 54 1010 1100
7 0110 0000 23 0110 1000 39 0110 0100 55 0110 1100
8 1110 0000 24 1110 1000 40 1110 0100 56 1110 1100
9 0001 0000 25 0001 1000 41 0001 0100 57 0001 1100
10 1001 0000 26 1001 1000 42 1001 0100 58 1001 1100
11 0101 0000 27 0101 1000 43 0101 0100 59 0101 1100
12 1101 0000 28 1101 1000 44 1101 0100 60 1101 1100
13 0011 0000 29 0011 1000 45 0011 0100 61 0011 1100
14 1011 0000 30 1011 1000 46 1011 0100 62 1011 1100
15 0111 0000 31 0111 1000 47 0111 0100 63 0111 1100
16 1111 0000 32 1111 1000 48 1111 0100 64 1111 1100