GE EPM 6000 Multi-function Power Metering System Power Screwdriver User Manual


 
CHAPTER 5: COMMUNICATIONS
EPM 6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE 5–3
0459 - 045A VAR-hours, Total SINT32 0 to 99999999 VARh per energy format
2
045B - 045C VA-hours, Total SINT32 0 to 99999999 VAh per energy format * see note 10
2
Block Size:
18
Primary Demand Block (IEEE Floating Point)
read-only
07CF - 07D0 Amps A, Average FLOAT 0 to 9999 M amps
2
07D1 - 07D2 Amps B, Average FLOAT 0 to 9999 M amps
2
07D3 - 07D4 Amps C, Average FLOAT 0 to 9999 M amps
2
07D5 - 07D6
Positive Watts, 3-Ph,
Average
FLOAT -9999 M to +9999 M watts
2
07D7 - 07D8
Positive VARs, 3-Ph,
Average
FLOAT -9999 M to +9999 M VARs
2
07D9 - 07DA
Negative Watts, 3-Ph,
Average
FLOAT -9999 M to +9999 M watts
2
07DB - 07DC
Negative VARs, 3-Ph,
Average
FLOAT -9999 M to +9999 M VARs
2
07DD - 07DE VAs, 3-Ph, Average FLOAT -9999 M to +9999 M VAs
2
07DF - 07E0 Positive PF, 3-Ph, AverageFLOAT -1.00 to +1.00 none
2
07E1 - 07E2
Negative PF, 3-PF,
Average
FLOAT -1.00 to +1.00 none
2
Block Size:
20
Primary Minimum Block (IEEE Floating Point)
read-only
0BB7 - 0BB8 Volts A-N, Minimum FLOAT 0 to 9999 M volts
2
0BB9 - 0BBA Volts B-N, Minimum FLOAT 0 to 9999 M volts
2
0BBB - 0BBC Volts C-N, Minimum FLOAT 0 to 9999 M volts
2
0BBD - 0BBE Volts A-B, Minimum FLOAT 0 to 9999 M volts
2
0BBF - 0BC0 Volts B-C, Minimum FLOAT 0 to 9999 M volts
2
0BC1 - 0BC2 Volts C-A, Minimum FLOAT 0 to 9999 M volts
2
0BC3 - 0BC4
Amps A, Minimum Avg
Demand
FLOAT 0 to 9999 M amps
2
0BC5 - 0BC6
Amps B, Minimum Avg
Demand
FLOAT 0 to 9999 M amps
2
0BC7 - 0BC8
Amps C, Minimum Avg
Demand
FLOAT 0 to 9999 M amps
2
0BC9 - 0BCA
Positive Watts, 3-Ph,
Minimum Avg Demand
FLOAT 0 to +9999 M watts
2
0BCB - 0BCC
Positive VARs, 3-Ph,
Minimum Avg Demand
FLOAT 0 to +9999 M VARs
2
0BCD - 0BCE
Negative Watts, 3-Ph,
Minimum Avg Demand
FLOAT 0 to +9999 M watts
2
0BCF - 0BD0
Negative VARs, 3-Ph,
Minimum Avg Demand
FLOAT 0 to +9999 M VARs
2
0BD1 - 0BD2
VAs, 3-Ph, Minimum Avg
Demand
FLOAT -9999 M to +9999 M VAs
2
0BD3 - 0BD4
Positive Power Factor, 3-
Ph, Minimum Avg
Demand
FLOAT -1.00 to +1.00 none
2
0BD5 - 0BD6
Negative Power Factor, 3-
Ph, Minimum Avg
Demand
FLOAT -1.00 to +1.00 none
2
0BD7 - 0BD8 Frequency, Minimum FLOAT 0 to 65.00 Hz
2
Block Size:
34
Primary Maximum Block (IEEE Floating Point)
read-only
0C1B - 0C1C Volts A-N, Maximum FLOAT 0 to 9999 M volts
2
0C1D - 0C1E Volts B-N, Maximum FLOAT 0 to 9999 M volts
2
0C1F - 0C20 Volts C-N, Maximum FLOAT 0 to 9999 M volts
2
0C21 - 0C22 Volts A-B, Maximum FLOAT 0 to 9999 M volts
2
0C23 - 0C24 Volts B-C, Maximum FLOAT 0 to 9999 M volts
2
0C25 - 0C26 Volts C-A, Maximum FLOAT 0 to 9999 M volts
2
0C27 - 0C28
Amps A, Maximum Avg
Demand
FLOAT 0 to 9999 M amps
2
0C29 - 0C2A
Amps B, Maximum Avg
Demand
FLOAT 0 to 9999 M amps
2
0C2B - 0C2C
Amps C, Maximum Avg
Demand
FLOAT 0 to 9999 M amps
2
0C2D - 0C2E
Positive Watts, 3-Ph,
Maximum Avg Demand
FLOAT 0 to +9999 M watts
2
HEX
ADDRESS
DESCRIPTION
1
FORMAT RANGE
6
UNITS OR
RESOLUTION
COMMENTS # REG