CHAPTER 5: COMMUNICATIONS
EPM 6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE 5–11
15
Maximum average positive three-phase
real power demand
SINT16 –32768 to +32767 W (4500/32768)
16
Maximum average positive three-phase
reactive power demand
SINT16 –32768 to +32767 var (4500/32768)
17
Maximum average negative three-phase
real power demand
SINT16 –32768 to +32767 W (4500/32768)
18
Maximum average negative three-phase
reactive power demand
SINT16 –32768 to +32767 var (4500/32768)
19
Maximum average three-phase apparent
power demand
SINT16 –32768 to +32767 VA (4500/32768)
30 5 20 Phase A current angle SINT16 –1800 to 1800° 0.1
21 Phase B current angle SINT16 –1800 to 1800° 0.1
22 Phase C current angle SINT16 –1800 to 1800° 0.1
23 Phase A-B voltage angle SINT16 –1800 to 1800° 0.1
24 Phase B-C voltage angle SINT16 –1800 to 1800° 0.1
25 Phase C-A voltage angle SINT16 –1800 to 1800° 0.1
26 CT numerator SINT16 1 to 9999 N/A See note 8
27 CT multiplier SINT16 1, 10, or 100 N/A
28 CT denominator SINT16 1 or 5 N/A
29 PT numerator SINT16 1 to 9999 N/A See note 9
30 PT multiplier SINT16 1, 10, or 100 N/A
31 PT denominator SINT16 1 to 9999 N/A
Internal Indication
80 1 0 Device restart bit N/A N/A N/A See note 10
Table 5–1: DNP Point Mapping (Sheet 2 of 2)
Object Var Point Description Format Range/units Multiplier Comments