5–4 EPM 6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE
CHAPTER 5: COMMUNICATIONS
0C2F - 0C30
Positive VARs, 3-Ph,
Maximum Avg Demand
FLOAT 0 to +9999 M VARs
2
0C31 - 0C32
Negative Watts, 3-Ph,
Maximum Avg Demand
FLOAT 0 to +9999 M watts
2
0C33 - 0C34
Negative VARs, 3-Ph,
Maximum Avg Demand
FLOAT 0 to +9999 M VARs
2
0C35 - 0C36
VAs, 3-Ph, Maximum Avg
Demand
FLOAT -9999 M to +9999 M VAs
2
0C37 - 0C38
Positive Power Factor, 3-
Ph, Maximum Avg
Demand
FLOAT -1.00 to +1.00 none
2
0C39 - 0C3A
Negative Power Factor, 3-
Ph, Maximum Avg
Demand
FLOAT -1.00 to +1.00 none
2
0C3B - 0C3C Frequency, Maximum FLOAT 0 to 65.00 Hz
2
Block Size:
34
THD Block
7, 13
read-only
0F9F - 0F9F Volts A-N, %THD UINT16 0 to 9999, or 65535 0.1%
1
0FA0 - 0FA0 Volts B-N, %THD UINT16 0 to 9999, or 65535 0.1%
1
0FA1 - 0FA1 Volts C-N, %THD UINT16 0 to 9999, or 65535 0.1%
1
0FA2 - 0FA2 Amps A, %THD UINT16 0 to 9999, or 65535 0.1%
1
0FA3 - 0FA3 Amps B, %THD UINT16 0 to 9999, or 65535 0.1%
1
0FA4 - 0FA4 Amps C, %THD UINT16 0 to 9999, or 65535 0.1%
1
0FA5 - 0FA5
Phase A Current 0th
harmonic magnitude
UINT16 0 to 65535 none
1
0FA6 - 0FA6
Phase A Current 1st
harmonic magnitude
UINT16 0 to 65535 none
1
0FA7 - 0FA7
Phase A Current 2nd
harmonic magnitude
UINT16 0 to 65535 none
1
0FA8 - 0FA8
Phase A Current 3rd
harmonic magnitude
UINT16 0 to 65535 none
1
0FA9 - 0FA9
Phase A Current 4th
harmonic magnitude
UINT16 0 to 65535 none
1
0FAA - 0FAA
Phase A Current 5th
harmonic magnitude
UINT16 0 to 65535 none
1
0FAB - 0FAB
Phase A Current 6th
harmonic magnitude
UINT16 0 to 65535 none
1
0FAC - 0FAC
Phase A Current 7th
harmonic magnitude
UINT16 0 to 65535 none
1
0FAD - 0FAD
Phase A Voltage 0th
harmonic magnitude
UINT16 0 to 65535 none
1
0FAE - 0FAE
Phase A Voltage 1st
harmonic magnitude
UINT16 0 to 65535 none
1
0FAF - 0FAF
Phase A Voltage 2nd
harmonic magnitude
UINT16 0 to 65535 none
1
0FB0 - 0FB0
Phase A Voltage 3rd
harmonic magnitude
UINT16 0 to 65535 none
1
0FB1 - 0FB8
Phase B Current
same as Phase A Current 0th to 7th harmonic magnitudes
8
0FB9 - 0FBC
Phase B Voltage
same as Phase A Voltage 0th to 3rd harmonic magnitudes
4
0FBD - 0FC4
Phase C Current
same as Phase A Current 0th to 7th harmonic magnitudes
8
0FC5 - 0FC8
Phase C Voltage
same as Phase A Voltage 0th to 3rd harmonic magnitudes
4
Block Size:
42
Phase Angle Block
14
read-only
1003 - 1003 Phase A Current SINT16 -1800 to +1800 0.1 degree
1
1004 - 1004 Phase B Current SINT16 -1800 to +1800 0.1 degree
1
1005 - 1005 Phase C Current SINT16 -1800 to +1800 0.1 degree
1
1006 - 1006 Angle, Volts A-B SINT16 -1800 to +1800 0.1 degree
1
1007 - 1007 Angle, Volts B-C SINT16 -1800 to +1800 0.1 degree
1
1008 - 1008 Angle, Volts C-A SINT16 -1800 to +1800 0.1 degree
1
Block Size:
6
HEX
ADDRESS
DESCRIPTION
1
FORMAT RANGE
6
UNITS OR
RESOLUTION
COMMENTS # REG