Quinny 65040-AB Air Compressor User Manual


 
Section VIII - Power$ync II
Operation
Quincy Compressor
®
- QSD 51
Press F2 at the Compressor Setup Menu to access the
Maintenance Menus. There are four main Compressor
Maintenance Menus that allow the operator to check or
reset maintenance hourmeters, time and date, view
diagnostics, and set modem baud rate. The operator can
also access the compressor configuration information.
Once in the Compressor Maintenance Menu, use the UP
and DOWN arrow keys to move between menus.
Compressor Maintenance Menu 1 contains maintenance
hourmeters and time and date information.
COMPRESSOR MAINTENANCE MENU 1
MAINTENANCE HOURMETERS PRESS F1
TIME AND DATE PRESS F2
UP FOR NEXT MENU/DOWN FOR PREVIOUS MENU
To access maintenance hourmeters, press F1. To
move to another maintenance menu, press the UP
arrow key.
The Compressor Hourmeter Menu allows access to
compressor hourmeters that include loaded hours,
unloaded hours, lubricant hours, line filter hours, intake
filter hours, and lubricant filter hours. It also allows these
hourmeters to be reset when maintenance is performed.
COMPRESSOR HOURMETER MENU
COMPRESSOR HOURMETERS PRESS F1
FILTER SERVICE HOURMETERS PRESS F2
RESET SERVICE HOURMETERS PRESS F3
Press F1 to access loaded and unloaded, lubricant
and line filter hourmeters. Press ENTER to return
to the previous display.
LOADED HOURS _____ UNLOADED HOURS _____
HOURS SINCE LAST FLUID CHANGE _____
******************************************
PRESS ENTER TO RETURN
This display shows the number of hours that the
compressor has been running at some load level
and the number of hours that the compressor has
been running unloaded. Logging these hourmeter
readings will help determine if changes to
sequence or schedule routines should be made in
network applications. Logging fluid hours and
comparing them to the results of the fluid analysis
will allow the advance scheduling of fluid changes.
Comparing fluid hours to analysis reports and
temperature logs will also aid in diagnosing
ambient conditions which might be shortening fluid
life. Press ENTER to return to the hourmeter
menu.
Press F2 at the Compressor Hourmeter Menu to access
the filter hourmeters.
INTAKE FILTER HOURS _________
LINE FILTER HOURS ____________
*******************************
PRESS ENTER TO RETURN
Inlet filter, and fluid filter hours can be logged to
help anticipate preventative maintenance. Line
filter hours refers to the control line filter that
assures clean air to the pneumatic controls on the
compressor package. This hourmeter is a
reminder that, although there is no element to
change and the filter automatically drains, its
operation should be checked periodically. An
improperly operating control line filter will affect
the proper operation of the compressor controls.
Press ENTER to return to the Compressor
Hourmeter Menu.