Quinny 65040-AB Air Compressor User Manual


 
Section VIII - Power$ync II
Operation
Quincy Compressor
®
- QSD 55
compressor, make sure the load time seconds never
go below 15 and unload time seconds are always
more than 2. This can be accomplished by sizing
air storage correctly for your system demand
needs. Use the UP arrow key to move to the next
display. Press ENTER to return to Compressor
Maintenance Menu 2.
P CALIBRATION DATE: 09/27/00
T CALIBRATION DATE: 09/27/00
UNIT CONFIGURATION DATE: 09/27/00
CURRENT TIME/DATE 00:00 09/27/00
The P CALIBRATION DATE is the date that the
pressure transducers were calibrated. The T
CALIBRATION DATE is the date that the
temperature sensors were calibrated. These dates
should be within one or two months of the unit
configuration date. If not, it is possible that the
sensors have been recalibrated since the machine
left the factory, which may affect the safe operation
and warranty of the compressor. Contact your
local Quincy service representative to assure that
the compressor is operating properly. Use the UP
arrow key to move to the next display. Press
ENTER to return to Compressor Maintenance
Menu 2.
From Compressor Maintenance Menu 2 press the UP
arrow key to access Compressor Maintenance Menu 3.
This menu allows the user to set the modem baud rate, if the
Modem Communications Package has been installed.
COMPRESSOR MAINTENANCE MENU 3
SET MODEM BAUD RATE PRESS F1
COMPRESSOR DIAGNOSTIC MENU PRESS F2
UP FOR NEXT MENU/DOWN FOR PREVIOUS MENU
Press F1 to set the modem baud rate.
Changes to the modem baud rate setting should only be
made if the standard modem that is part of the Modem
Communications Package option is being replaced with a
different model. The correct baud rate for the factory
modem is 2400. Changing the baud rate from the factory
setting may adversely affect communications.
MODEM BAUD RATE SETUP
SET BAUD RATE _______
PRESS ENTER TO RETURN
Use the UP or DOWN arrow keys to adjust the
baud rate to the desired specification. 2400 Baud
is the recommended setting. Press ENTER to
accept and return to Compressor Maintenance
Menu 3.
Press F2 at Compressor Maintenance Menu 3 to view the
Compressor Diagnostic Menu:
COMPRESSOR DIAGNOSTIC MENU
VIEW SHUTDOWN LOG PRESS F1
NETWORK DIAGNOSTIC PRESS F2
TRANSDUCER PARAMETER CHECK PRESS F3
Press F1 to view the shutdown log.
ENTRY: 01 TIME: 20:16 DATE: 09/27/00
SHUTDOWN CODE: CONTACTOR FAULTY
USE UP/DOWN KEYS TO VIEW OTHER ENTRIES
PRESS ENTER TO RETURN
This display shows shutdown and service alarms
beginning with the most recent event. It indicates the
entry number, time of the entry, date of the entry and
nature of the shutdown or service alarm. Use the UP or
DOWN arrow keys to view other entries. The log will
hold the 16 most recent alarm conditions. As new alarm
conditions occur, the computer will drop the oldest and
add the newest. A new machine may have entries in the
log resulting from the assembly testing stages.