Bryant 580J*08--14D Air Compressor User Manual


 
44
SW3 Protocol Selection
PROTOCOL DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1
BACnet MS/TP
(Master)
Unused OFF OFF OFF ON OFF Select Baud Select Baud
Modbus
(Slave)
Unused OFF OFF ON ON OFF Select Baud Select Baud
N2
(Slave)
Unused OFF OFF OFF ON ON OFF OFF
LonWorks Unused ON ON OFF ON OFF OFF OFF
NOTE:
DS = Dip Switch
BACnet MS/TP SW3 example shown
Baud Rate Selections
BAUD RATE DS2 DS1
9600 OFF OFF
19,200 ON OFF
38,400 OFF ON
76,800 ON ON
C07166
Fig. 57 -- RTU--MP SW3 Dip Switch Settings
Virtual BACview
Vi rtual BACview is a freeware compute r program that
functions as the BACview
6
Handheld. The USB Link
interface (USB--L) is required to connect a computer to
the RTU--MP board. The link cable connects a USB port
to the J12 local access port. This program functions and
operates identical to the handheld.
RTU--MP Troubleshooting
Communication LEDs
The LEDs indicate if the controller is speaking to the
devic es on the network. The LEDs should reflect
communication traffic based on the baud rate set. The
higher the baud rate the more solid the LEDs will appear.
C07170
Fig. 58 -- BACview
6
Handheld Connections