Bryant 580J*08--14D Air Compressor User Manual


 
74
APPENDIX II. PHYSICAL DATA (cont.)
Physical Data (Heating) 7.5 -- 12.5TONS
580J**08 580J**12 580J**14
Gas Connection
#ofGasValves 1 1 1
Nat. gas supply line press (in. w.g.)/(PSIG) 4 --- 13 / 0.18 --- 0.47 4 --- 13 / 0.18 --- 0.47 4--- 13 / 0.18 --- 0.47
LP supply line press (in. w.g.)/(PSIG) 11---13 / 0.40---0.47 11---13 / 0 .40---0.47 11---13 / 0.40---0.47
Heat Anticipator Setting (Amps)
1st stage 0.14 0.14 0.14
2nd stage 0.14 0.14 0.14
Natural Gas Heat, Liquid Propane Heat
#ofstages/#ofburners(total) 1/3 2/4 2/4
LOW
Connection size 1/2” NPT 3/4” NPT 3/4” NPT
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115
Temperature rise (min/max) 20 --- 50 25 --- 65 25 --- 65
#ofstages/#ofburners(total) 2/4 2/5 2/5
MED
Connection size 3/4” NPT 3/4” NPT 3/4” NPT
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115
Temperature rise (min/max) 35 --- 65 30 --- 65 25 --- 65
#ofstages/#ofburners(total) 2/5 2/5 2/5
HIGH
Connection Size 3/ 4” NPT 3/4” NPT 3/4” NPT
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115
Temperature rise (min/max) 45 --- 75 35 --- 70 35 --- 70
580J