Lincoln Electric SVM 122-A Welder User Manual


 
FIGURE C.4 – NA-3 WIRE FEEDER
CONNECTION TO THE IDEALARC DC-400
5. Extend wire feeder control cable lead #21 so it can
be connected directly to the work piece.
a. Make a bolted connection using AWG #14 or
larger insulated wire. Tape the bolted connec-
tion with insulating tape.
b. An S-16586- X remote voltage sensing work
lead is available for this purpose.
c. Keep the #21 lead electrically separate from
the work cable circuit and connection.
d. Tape the #21 lead to work cable for ease of
use.
NOTE: The connection diagram shown in Figure C.4
shows the electrode connected for positive
polarity. To change polarity:
a. Set the Idealarc DC-400 POWER toggle
switch to the OFF (0) position.
b. Move the electrode cable to the negative (-)
output terminal.
c. Move the work cable to the positive (+) output
terminal.
d. Set the VOLTMETER toggle switch to nega-
tive (-).
6. Set the DC-400 OUTPUT CONTROL switch to the
“Remote” position and the OUTPUT TERMINALS
switch in the “Remote” position.
CONNECTING THE NA-5 TO THE
IDEALARC DC-400 (TERMINAL STRIP)
1. Disconnect main AC input power to the Idealarc
DC-400.
2. Set the Idealarc DC-400 POWER toggle switch to
the OFF (0) position.
3. Connect the wire feeder control cable leads to the
Idealarc DC-400 terminal strip as shown in Figure
C.5.
FIGURE C.5 – NA-5 WIRE FEEDER
CONNECTION TO THE IDEALARC DC-400
NOTE: If using a K215 control cable, connect
control cable leads #75, #76, and #77 to
the matching #75, #76, and #77 terminals
on the terminal strip of the Idealarc DC-
400.
4. Connect the wire feeder control cable ground lead
to the frame terminal marked .
NOTE: The Idealarc DC-400 must be properly
grounded.
ACCESSORIES
C-7 C-7
LINCOLN
®
ELECTRIC
IDEALARC DC-400
Return to Section TOC Return to Section TOC Return to Section TOC Return to Section TOC
Return to Master TOC Return to Master TOC Return to Master TOC Return to Master TOC