APC Battery Management System Battery Charger User Manual


 
®
USER’S GUIDE
Battery Management System
97
Battery Management System events
Code Severity Description
0x0801 Informational System: Communication established.
0x0802 Severe System: Communication lost.
0x080D Informational System: Configuration has been changed.
0x080E Severe Charger: String voltage is low.
0x080F Informational Charger: Low string voltage returned to normal.
0x0810 Severe Charger: String voltage is high.
0x0811 Informational Charger: High string voltage returned to normal.
0x0812 Warning Charger: High ripple current.
0x0813 Informational Charger: High ripple current returned to normal.
0x0814 Severe Charger: String discharging. See Discharge cycle counter.
0x0815 Informational Charger: String no longer discharging.
0x0816 Severe Battery: Cell shorted.
0x0817 Informational Battery: Cell short cleared.
0x0818 Warning Management Controller: Open fuse or connection.
0x0819 Informational Management Controller: Open fuse or connection normal.
0x081A Severe Battery: Capacity is low.
0x081B Informational Battery: Low capacity is now normal.
0x081C Warning Battery: Ohmic value is high.
0x081D Informational Battery: High ohmic value is now normal.
0x081E Severe Battery: Thermal runaway in progress.
0x081F Informational Battery: Thermal runaway no longer in progress.
0x0820 Warning Battery: Dryout/sulfation present.