USER’S GUIDE
Battery Management System
165
To use Secure CoPy (SCP) to upgrade the firmware for one Battery
Management System Management Card:
1. Identify and locate the firmware modules described in the preceding
instructions for FTP.
2. Use an SCP command line to transfer the AOS firmware module to the
Battery Management System. The following example assumes a
Battery Management System IP address of 158.205.6.185, and an
AOS module of apc_hw02_aos_264.bin.)
scp apc_hw02_aos_264.bin apc@158.205.6.185:apc_hw02_aos_264.bin
3. Use a similar SCP command line, with the name of the application
module instead of the AOS module, to transfer the application module
to the Battery Management System.