2-12
Cisco ASR 903 Router Hardware Installation Guide
OL-25178-04
Chapter 2 Preparing for Installation
Site Planning
Air Flow Guidelines for Enclosed Rack Installation
To install a Cisco ASR 903 Router in a 4-post enclosed cabinet, the front and rear doors of the cabinet
must be removed or be perforated with a minimum of 65% open area (70% for ETSI 800mm racks).
If you are mounting the chassis in a 4-post enclosed cabinet, ensure that you have a minimum of 6 inches
(15.24 cm) of clearance on each side of the chassis.
Floor Loading Considerations
Ensure that the floor under the rack supporting the Cisco ASR 903 Routers is capable of supporting the
combined weight of the rack and all the other installed equipment.
To assess the weight of a fully configured Cisco ASR 903 Router, refer to “System Specifications”
section on page 1-2.
For additional information about floor loading requirements, consult GR-63-CORE, Network Equipment
Building System (NEBS) Requirements: Physical Protection.
Site Power Guidelines
The Cisco ASR 903 Router has specific power and electrical wiring requirements. Adhering to these
requirements ensures reliable operation of the system. Follow these precautions and recommendations
when planning your site power for the Cisco ASR 903 Router:
• The redundant power option provides a second, identical power supply to ensure that power to the
chassis continues uninterrupted if one power supply fails or input power on one line fails.
• In systems configured with the redundant power option, connect each of the two power supplies to
a separate input power source. If you fail to do this, your system might be susceptible to total power
failure due to a fault in the external wiring or a tripped circuit breaker.
• To prevent a loss of input power, be sure that the total maximum load on each circuit supplying the
power supplies is within the current ratings of the wiring and the breakers.
• Check the power at your site before installation and periodically after installation to ensure that you
are receiving clean power. Install a power conditioner if necessary.
• Provide proper grounding to avoid personal injury and damage to the equipment due to lightning
striking power lines or due to power surges. The chassis ground must be attached to a central office
or other interior ground system.
Caution This product requires short-circuit (overcurrent) protection, to be provided as part of the building
installation. Install only in accordance with national and local wiring regulations.
Note The Cisco ASR 903 Router installation must comply with all the applicable codes and is approved for
use with copper conductors only. The ground bond fastening hardware should be of compatible material
and preclude loosening, deterioration, and electrochemical corrosion of hardware and joined material.
Attachment of the chassis ground to a central office or other interior ground system must be made with
a 6 AWG gauge wire, copper ground conductor at a minimum.