Chapter 3 Installing the Cisco ASR 903 Router
Installing the Power Supply
Step 5 Use a ratcheting torque screwdriver to torque the terminal block plug captive screw (above the installed
wire lead) from 4.425 in.-lb (.5 N-m) to 5.310 in-lb (.6 N-m) as shown in Figure 3-18.
Figure 3-18 Torquing the DC Power Supply Terminal Block Plug Screws
Step 6 Repeat Step 4 through Step 5 for the remaining DC input power source wire and the ground wire.
Figure 3-19 shows the wiring completed for a terminal block plug.
Figure 3-19 Inserting the DC Power Supply Terminal Block Plug in the Block Header
1 Torque is from 4.425 in.-lb (.5 N-m) to 5.310 in-lb (.6 N-m).
207764
1
1 DC power supply ground lead wire 3 DC power supply positive (+) lead wire
2 DC power supply negative (-) lead wire