Mitsubishi Electronics FX1S Welding System User Manual


 
FX Series Programmable Controllers Devices in Detail 4
4-9
4.4.4 Annunciator Flags
Some state flags can be used as outputs for external diagnosis (called annunciation) when
certain applied instructions are used. These instructions are;
ANS function 46: ANnunciator Set - see page 5-47
ANR function 47: ANnunciator Reset - see page 5-47
When the annunciator function is used the controlled state flags are in the range S900 to S999
(100 points). By programming an external diagnosis circuit as shown below, and monitoring
special data register D8049, the lowest activated state from the annunciator range will be
displayed.
Each of the states can be assigned to signify an error or fault condition. As a fault occurs the
associated state is driven ON. If more than one fault occurs simultaneously, the lowest fault
number will be displayed. When the active fault is cleared the next lowest fault will then be
processed.
This means that for a correctly prioritized diagnostic system the most dangerous or damaging
faults should activate the lowest state flags, from the annunciator range. All state flags used for
the annunciator function fall in the range of battery backed/ latched state registers.
Monitoring is enabled by driving special auxiliary
relay M8049 ON.
State S900 is activated if input X0 is not driven
within one second after the output Y0 has been
turned ON.
State S901 is activated when both inputs X1 and
X2 are OFF for more than two seconds.
If the cycle time of the controlled machine is less
than ten seconds, and input X3 stays ON, state
S902 will be set ON if X4 is not activated within
this machine cycle time.
If any state from S900 to S999 is activated, i.e.
ON, special auxiliary relay M8048 is activated to
turn on failure indicator output Y10.
The states activated by the users error / failure
diagnosis detection program, are turned OFF by
activating input X5. Each time X5 is activated, the
active annunciator states are reset in ascending
order of state numbers.
M8000
Y0 X0
S900K10T0ANS
X1 X2
S901K20T1ANS
X3 X4
S902K100T2ANS
FNC46
FNC46
FNC46
M8048
X5
ANR (P)
FNC47
Y10
M8049