4.2.45 OL signal output timer (Pr. 157)
Pr. 157 "OL signal waiting time"
Use this parameter to set whether the overload alarm signal (OL signal) is output immediately or a preset
period of time after occurrence of an overload status.
Parameter
Number
Factory
Setting
Setting Range Remarks
157 0 0 to 25 s, 9999 9999: No signal output
Set time (s)
Overload status (OL output)
OL output signal
<Setting>
Refer to the following table and set the parameter:
Pr. 157
Setting
Description
0 Output immediately.
0.1 to 25 Output after the set time (s) has elapsed.
9999 Overload alarm signal is not output.
Pr. 158
%
%%
%
Refer to Pr. 54.
Pr. 190 "RUN terminal function
selection"
Pr. 191 "SU terminal function selection"
Pr. 192 "IPF terminal function selection"
Pr. 193 "OL terminal function selection"
Pr. 194 "FU terminal function selection"
Pr. 195 "A, B, C terminal function selection"
Related parameters