PARAMETERS
138
Pr. 52 "DU/PU main display data
selection"
Related
p
arameter
Note: 1. Pr. 77, Pr. 160 and Pr. 991 values can always be read independently of the user group setting.
2. When Pr. 173 or Pr. 174 is read, the number of parameters registered to user group 1 appears.
When Pr. 175 or Pr. 176 is read, the number of parameters registered to user group 2 appears.
3. "0" set in the second digit of the 2-digit Pr. 160 setting is not displayed. However, it is displayed
when "0" is set in the first digit only.
4. When "9999" is set in Pr. 174 or Pr. 176, the parameters registered to the corresponding user
group is batch-deleted.
Pr. 162 to Pr. 165
%
%%
%
Refer to Pr. 57.
4.2.47 Watt-hour meter clear/actual operation hour meter clear
(Pr. 170, Pr. 171)
Pr. 170 "watt-hour meter clear"
Pr. 171 "actual operation hour meter clear"
You can clear the watt-hour value and actual operation hour monitoring function.
Parameter
Number
Factory
Setting
Setting Range
170 0 0
171 0 0
<Setting>
Write "0" in the parameters to clear the watt-hour value and actual operation hour.
REMARKS
The watt-hour value is monitored at the Pr. 52 setting of "25", and the actual operation hour at the Pr. 52
setting of "23".
Pr. 173 to Pr. 176
%
%%
%
Refer to Pr. 160.
4.2.48 Input terminal function selection (Pr. 180 to Pr. 186)
Pr. 180 "RL terminal function selection"
Pr. 181 "RM terminal function selection"
Pr. 182 "RH terminal function selection"
Pr. 183 "RT terminal function selection"
Pr. 184 "AU terminal function selection"
Pr. 185 "JOG terminal function selection"
Pr. 186 "CS terminal function selection"
Use these parameters to select/change the input terminal functions.
Parameter
Number
Terminal
Symbol
Factory
Setting
Factory-Set Terminal Function Setting Range
180 RL 0 Low-speed operation command (RL)
181 RM 1 Middle-speed operation command (RM)
182 RH 2 High-speed operation command (RH)
183 RT 3 Second function selection (RT)
184 AU 4 Current input selection (AU)
185 JOG 5 Jog operation selection (JOG)
186 CS 6
Automatic restart after instantaneous
power failure selection (CS)
0 to 7, 10 to 14,
16, 17, 9999
(24 may also be set
for the NA and EC
versions only.)