PARAMETERS
152
<Output stop detection>
Td
STOP START
Tim
e
Tim
e
Motor
Pr. 508: Output stop
cancel level
Pr. 507: Output stop
level
Pr. 506: Output stop
detection time
Output at stop
Output frequency
Process value
#
The output stops if the output frequency continues to be lower than the Pr. 507 value for longer than the
time set in Pr. 506.
When the setting is 9999, the output stop function is not performed.
Also, an output stop is not detected when the process value is not more than the Pr. 508 value or when the
start signal is off. It is not detected during auxiliary motor operation either.
Parameter Number Name Setting Range Setting Increments Factory Setting
506 Output stop detection time 0 to 3600s, 9999 0.1s 9999
#
You can set the set the output frequency value at which an output stop is detected. The output is stopped
when the output frequency continues to be lower than the Pr. 507 value for longer than the time set in
Pr. 506.
Parameter Number Name Setting Range Setting Increments Factory Setting
507 Output stop detection level 0 to 120Hz 0.01Hz 0Hz
#
You can set the process value at which a restart is made after the output stop. Set the ratio of the process
value to the set point.
Parameter Number Name Setting Range Setting Increments Factory Setting
508
Output stop cancel process value
level
0 to 100% 0.1% 100%