106 RT-PRC031-EN
Mechanical Specifications
temperature control and VAV
Supply Air temperature control.
• VAV zone sensor shall be
provided with supply air single
temperature setpoint and AUTO/
OFF system switch. Status
indication LED lights shall
include: System On, Heat, Cool
and Service. Sensor shall be
provided for zone temperature
control with VAV units.
• Remote Sensor shall be available
to be used for remote zone
temperature sensing capabilities
when zone sensors are used as
Remote panels.
• Fast Warm-Up Sensor shall be
used as Morning warm-up
sensor with VAV units.
• Integrated Comfort™ System
sensors shall be available with
sensor only, sensor with timed
override, and sensor with local
temperature setpoint adjustment
with timed override.
• Remote Minimum Position
Potentiometer shall be available
to remotely adjust the minimum
position setting of the unit
economizer.
• Wireless Zone Sensor shall be
available with a RF wireless zone
temperature, setpoint and timed
override transmitter and a RF
receiver that connects directly to
the IntelliPak II controller and
uses spread spectrum
technology. Sensor battery life
shall provide at least 5 years life
under normal operating
conditions and shall provide a
readily visual indication of
battery condition.
CO
2
Sensing
•The CO
2
sensor shall have the
ability to monitor space
occupancy levels within the
building by measuring the parts
per million of CO
2
(Carbon
Dioxide) in the air. As the CO
2
levels increase, the outside air
damper modulates to meet the
CO
2
space ventilation
requirements.