Trane RT-PRC031-EN Impact Driver User Manual


 
106 RT-PRC031-EN
Mechanical Specifications
temperature control and VAV
Supply Air temperature control.
VAV zone sensor shall be
provided with supply air single
temperature setpoint and AUTO/
OFF system switch. Status
indication LED lights shall
include: System On, Heat, Cool
and Service. Sensor shall be
provided for zone temperature
control with VAV units.
Remote Sensor shall be available
to be used for remote zone
temperature sensing capabilities
when zone sensors are used as
Remote panels.
Fast Warm-Up Sensor shall be
used as Morning warm-up
sensor with VAV units.
Integrated Comfort™ System
sensors shall be available with
sensor only, sensor with timed
override, and sensor with local
temperature setpoint adjustment
with timed override.
Remote Minimum Position
Potentiometer shall be available
to remotely adjust the minimum
position setting of the unit
economizer.
Wireless Zone Sensor shall be
available with a RF wireless zone
temperature, setpoint and timed
override transmitter and a RF
receiver that connects directly to
the IntelliPak II controller and
uses spread spectrum
technology. Sensor battery life
shall provide at least 5 years life
under normal operating
conditions and shall provide a
readily visual indication of
battery condition.
CO
2
Sensing
•The CO
2
sensor shall have the
ability to monitor space
occupancy levels within the
building by measuring the parts
per million of CO
2
(Carbon
Dioxide) in the air. As the CO
2
levels increase, the outside air
damper modulates to meet the
CO
2
space ventilation
requirements.