46 RT-PRC031-EN
Performance Data — Supply Fan without Inlet Guide
Vanes (with or without Variable Frequency Drive)
CFM Total Static Pressure
Std. 4.25 4.50 4.75 5.00 5.25 5.50 5.75 6.00
Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
23000 1117 23.23 1138 24.39 1157 25.52 1177 26.71 1197 27.85 1216 29.06 1237 30.34 1255 31.57
24000 1138 24.74 1157 25.86 1175 26.99 1194 28.17 1213 29.36 1233 30.60 1251 31.78 1270 33.09
25000 1158 26.23 1177 27.41 1194 28.53 1213 29.77 1231 30.94 1250 32.24 1268 33.46 1286 34.73
26000 1180 27.86 1198 29.04 1215 30.22 1233 31.46 1250 32.69 1268 33.97 1286 35.24 1303 36.49
27000 1202 29.58 1219 30.77 1237 32.02 1254 33.31 1271 34.53 1288 35.80 1305 37.13 1321 38.35
28000 1224 31.30 1242 32.61 1259 33.92 1275 35.15 1292 36.42 1308 37.75 1325 39.05 1342 40.41
29000 1246 33.13 1263 34.43 1281 35.80 1297 37.09 1313 38.44 1330 39.83 1345 41.11 1361 42.44
30000 1270 35.09 1286 36.39 1303 37.83 1319 39.17 1336 40.58 1351 41.88 1367 43.31 1383 44.71
31000 1293 37.07 1310 38.50 1325 39.84 1341 41.25 1358 42.72 1374 44.17 1389 45.58 1404 46.95
32000 1316 39.21 1333 40.62 1348 42.02 1364 43.49 1381 45.03 1396 46.44 1411 47.92 1427 49.45
33000 1340 41.44 1357 42.92 1373 44.39 1388 45.83 1403 47.33 1418 48.81 1434 50.35 1448 51.84
34000 1365 43.77 1380 45.24 1396 46.77 1411 48.27 1427 49.84 1441 51.28 1457 52.87 1471 54.43
35000 1389 46.21 1405 47.75 1420 49.26 1435 50.83 1450 52.36 1465 53.96 1479 55.41 1494 57.12
36000 1412 48.60 1429 50.29 1444 51.86 1460 53.50 1473 55.00 1488 56.56 1503 58.28 1517 59.84
37000 1437 51.20 1452 52.86 1469 54.60 1483 56.20 1498 57.87 1512 59.38
38000 1461 53.92 1476 55.56 1492 57.26 1507 59.04
39000 1486 56.67 1501 58.39
40000 1511 59.68
CFM Total Static Pressure
Std. 6.25 6.50 6.75 7.00 7.25 7.50 7.75 8.00
Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
23000 1275 32.85 1295 34.21 1313 35.47 1332 36.79 1352 38.18 1369 39.44 1390 40.95 1408 42.32
24000 1288 34.33 1308 35.71 1326 37.00 1344 38.35 1363 39.76 1380 41.05 1400 42.58 1418 43.99
25000 1305 36.07 1322 37.32 1340 38.63 1358 40.01 1376 41.45 1393 42.76 1413 44.33 1430 45.76
26000 1321 37.79 1337 39.07 1355 40.41 1373 41.80 1391 43.26 1407 44.61 1424 46.00 1441 47.46
27000 1338 39.62 1355 41.03 1371 42.32 1389 43.76 1406 45.15 1423 46.61 1440 48.03 1456 49.52
28000 1358 41.74 1373 43.03 1389 44.37 1407 45.85 1422 47.20 1438 48.60 1454 50.04 1471 51.54
29000 1377 43.83 1394 45.26 1408 46.57 1423 47.91 1440 49.40 1456 50.84 1471 52.22 1487 53.77
30000 1398 46.06 1413 47.46 1429 48.91 1444 50.31 1459 51.76 1475 53.25 1488 54.58 1505 56.17
30000 1398 46.06 1413 47.46 1429 48.91 1444 50.31 1459 51.76 1475 53.25 1488 54.58 1505 56.17
31000 1420 48.46 1434 49.82 1449 51.23 1464 52.68 1479 54.19 1493 55.63 1508 57.11
32000 1441 50.83 1455 52.26 1470 53.72 1485 55.24 1500 56.80 1513 58.18 1528 5972
33000 1463 53.38 1478 54.87 1492 56.41 1507 57.99 1520 59.39
34000 1485 55.93 1499 57.47 1514 59.08
35000 1508 58.69
CFM Total Static Pressure
Std. 8.25 8.50 8.75 9.00
Air RPM BHP RPM BHP RPM BHP RPM BHP
23000 1428 43.75 1444 45.03 1464 46.53 1488 48.30
24000 1437 45.45 1453 46.74 1473 48.32 1490 49.71
25000 1447 47.14 1464 48.58 1482 50.06 1500 51.61
26000 1459 48.97 1477 50.55 1493 51.95 1509 53.40
27000 1473 50.95 1489 52.44 1504 53.87 1523 55.59
28000 1488 53.11 1503 54.51 1519 56.08 1536 57.71
29000 1504 55.37 1518 56.78 1533 58.25
30000 1519 57.58 1535 59.15
Notes:
1. Supply fan performance table includes internal resistance of air handler. For total static pressure determination, system external
static pressure must be added to appropriate component sp drops (chilled water coil, filters, optional economizer, optional
heating system).
2. Maximum SP leaving the air handler is 5.5" H
2
0 positive.
(i)
Outlined area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.
Table 15 Supply Fan Performance STANDARD CFM —Casing B (32")