Trane RT-PRC031-EN Impact Driver User Manual


 
98 RT-PRC031-EN
Options
Provided for those cases where
non-Tracer building
management system is used.
The GBAS module provides a
binary input for Demand
Limiting, four (4) analog inputs
for setpoint adjustment and five
(5) relay outputs for diagnostic
reporting. Inputs can use a
potentiometer or 0-5 vdc signal.
Generic Building Automation
System Module
(GBAS 0-10 vdc)—Used to
provide broad control
capabilities for building
automation systems other than
Trane's Tracer™ system.
The GBAS module provides a
binary input for Demand
Limiting, four (4) analog inputs
for setpoint adjustment and four
(4) analog outputs as well as one
(1) relay output for diagnostic
reporting. Inputs can use a
potentiometer or 0-10 vdc signal.
Remote Human Interface Panel
(RHI)—Remote Human Interface
Panel can perform all the same
functions as unit mounted
Human Interface Panel, except
for the Service Mode. Up to 4 air
handler units can be monitored
and controlled with a single
Remote Human Interface Panel.
This panel uses the same
attractive enclosure as the
Tracker™ building control panel.
With features such as a
2 line X 40 character clear
English display, a red LED light
to indicate an alarm condition
(alarm also shown on the two
line display), a simple 16 key
keypad that is used in
conjunction with the display to
prompt the infrequent user when
making desired changes and an
attractive hinged door makes the
RHI very suitable for mounting
on any wall.
The RHI can be mounted inside a
building, up to 5000 feet from
the unit. The RHI is wired to the
IPCB mounted in the air handler
with twisted wire pair
communication wiring and 24V
control wiring.
Ventilation Override Module
(VOM)—With the Ventilation
Override Module installed, the
unit can be programmed to
transition to up to 5 different
programmed sequences for
Smoke Purge, Evacuation,
Pressurization, Purge, Purge with
duct control sequence and Unit
off. The transition occurs when a
binary input on the VOM is
closed (shorted); this would
typically be a hard wired relay
output from a smoke detector or
fire control panel.
Inter-Processor Communication
Bridge (IPCB)—This module
provides an amplified and
filtered version of the IPC link for
connection to a Remote Human
Interface Panel. Each air handler
that is tied into a Remote Human
Interface Panel must have a IPCB
installed into it.
Trane LonTalk® Communication
Interface Module—Provides an
interface to the Trane Integrated
Comfort System (ICS), which
allows control and monitoring of
the air handler by a Tracer or 3rd
party building management
system utilizing LonTalk
protocol.
Field Installed Accessories
Electronic Zone Sensors
Zone Sensors—Two temperature
setpoint levers, heat, auto, off, or
cool system switch, fan auto or
fan on switch. Optional status
indication LED lights, System On,
Heat, Cool, and Service are
available. These sensors are
used with CV units.
Programmable Night Setback
Sensors—Electronic
programmable sensors with
auto or manual changeover with
seven day programming.
Keyboard selection of heat, cool,
fan auto or on. All
programmable sensors have
System On, Heat, Cool, Service
LED/indicators as standard.
Night setback sensors have (1)
Occupied, (1) Unoccupied and (2)
Override programs per day.
Models are available for CV zone
temperature control and VAV
supply air temperature control.
Zone Sensor—Sensor with
supply air single temperatures
setpoint and AUTO/OFF system
switch. Status indication LED
lights; System On, Heat, Cool,
and Service are provided.
Sensors are available to be used
with VAV units.
Remote Sensor—Can be used for
remote zone temperature
sensing capabilities when zone
sensors are used as remote
panels.
Full Warm-Up Sensor—Morning
warm-up sensor for use with
VAV units.
Integrated Comfort™ System
sensors—Used for zone
temperature sensing when
Tracer™ is communicating with
the air handler. The sensors are
available with options such as
sensor only, sensor with timed
override button, and a sensor
with local temperature
adjustment control, with timed
override button.
Remote Minimum Position
Potentiometer—Minimum
position setting of economizer
can be remotely adjusted with
this accessory.
Temperature Sensor—Bullet or
pencil type sensor that could be
used for temperature input such
as return air duct temperature.
Wireless Zone Sensor—The
Trane Wireless Zone has the
advantage of easy and flexible
installation and uses a radio that
is specifically designed for the
application. It includes sensor,
receiver, wiring harness, and two
AA lithium batteries. Standard
functions include zone
temperature, temperature
setpoint (in Fahrenheit or
Celsius), and occupied/
unoccupied override.
Inter-Processor Communication
Bridge kit—Included in this kit is
an Inter-Processor
Communicating Bridge (IPCB)
module which is required for
communication with a Remote
Human Interface Panel.
Remote Human Interface Panel
kit—Can control up to four air
handlers. The Remote Human
Interface Panel has all the
features of the Unit Mounted
Human Interface Panel, except