Trane RT-PRC031-EN Impact Driver User Manual


 
34 RT-PRC031-EN
Table 3 General Data (All dimensions in inches)
Casing A Casing B Casing C
Supply Fans Std CFM
Number/Size/Type
Number of Motors
HP Range
CFM Range/CFM at Max SP
Total SP Range-(In. WG)
1/25/ DW AF
1
15 - 50
16000-31000/22000
7.5
1/32/ DW AF
1
15 - 60
20000-38000/32000
7.5
1 / 36 DW AF
1
15 - 75
23000-45000/40000
7.5
Exhaust Fans Std CFM
Number/Size/Type
Number of Motors
HP Range
CFM Range/CFM at Max SP
ESP Range-(In. WG)
1/25/ DW FC
1
7.5 - 25 hp
10000-28000/24000
2.5
1/28/ DW FC
1
7.5 - 50 hp
13000-35000/30000
2.5
1 / 32 DW FC
1
15 - 60 hp
23000-40000/40000
2.5
Exhaust Fans Low CFM
Number/Size/Type
Number of Motors
HP Range
CFM Range/CFM at Max SP
ESP Range-(In. WG)
-
-
-
-
-
1/25/ DW FC
1
7.5 - 25 hp
10000-28000/24000
2.5
1/28/ DW FC
1
7.5 - 50 hp
13000-35000/30000
2.5
Return Fans Std CFM
Number/Size/Type
Number of Motors
HP Range
CFM Range/CFM at Max SP
ESP Range-(In. WG)
1/36/ Plenum
1
7.5 - 40 hp
16000-31000
2.5
1 / 40 Plenum AF
1
10 - 40 hp
20000-38000
2.5
1 / 44.5 Plenum AF
1
10 - 40 hp
23000- 44000/39000
2.5
Electric Heat (60 Hz)
kw
Circuit Capacity Steps
90-265
30 - 37.5 kW
90-300
30 - 37.5 kW
140-300
35 - 37.5 kW
Natural Gas Heat
2-Stage Gas Heat
Low Heat Input (MBH)
Mid Heat Input/Output (MBH)
High Heat Input/Output (MBH)
Standard Heating Capacity Steps
850
1100
1800
2
850
1100
1800
2
850
1100
1800
2
Fully Modulating Steps
Low Heat Input (MBH)
Mid Heat Input (MBH)
High Heat Input (MBH)
10:1
20:1
20:1
10:1
20:1
20:1
10:1
20:1
20:1
Heat Exchanger Material Stainless Steel Stainless Steel Stainless Steel
Chilled Water Coil
Size (inches) 42 x 115 42 x 115 42 x 115
Rows 2, 4, 6, or 8 2, 4, 6, or 8 2, 4, 6, or 8
Quantity 2 2 2
Type 5W, W, or WD 5W, W, or WD 5W, W, or WD
Fin Series 80, 108, 144, or 168 80, 108, 144, or 168 80, 108, 144, or 168
Turbulators Turbulators Available Turbulators Available Turbulators Available
Hot Water Coil
Size
Quantity
Type
High Heat (fins/ft)
Low Heat (fins/ft)
33 x 88 x 2 rows
2
5W, PrimaFlo
122
80
33 x 88 x 2 rows
2
5W, PrimaFlo
122
80
33 x 88 x 2 rows
2
5W, PrimaFlo
122
80
Steam Coil
Size
Quantity
Type
High Heat (fins/ft)
Low Heat (fins/ft)
33 x 88 x 1 row
2
NS, SigmaFlo
112
62
33 x 88 x 1 row
2
NS, SigmaFlo
112
62
33 x 110 x 1 row
2
NS, SigmaFlo
112
62
General Data