Agilent Technologies 6814B Welding System User Manual


 
IEC Mode Command Summary - E
169
CALCulate:INTegral:TIME
This command selects the Pst integration time for IEC Flicker measurements. The parameter may only
assume values of 1, 5, 10, and 15 minutes in accordance with IEC 868. The command will be accepted
and may be queried, but will have no meaningful function unless the ac source is placed in IEC mode
using the SYSTem:CONFigure command.
Command Syntax
CALCulate:INTegral:TIME <NRf+>
Parameters
1, 5, 10, & 15 minutes
*RST Value
10 minutes
Examples
CALC:INT:TIME 10
Query Syntax
CALCulate:INTegral:TIME?
Returned Parameters
<NR3>
Related Commands
SYSTEM:CONF MEAS:ARR:VOLT:FLUC:FLIC?
MEAS:ARR:VOLT:FLUC:PST?
MEAS:ARR:VOLT:FLUC:ALL?
CALCulate:SMOothing
This command turns on or off a smoothing filter for current harmonic measurements. The filter transfer
function is equivalent to a single pole lowpass function with a 1.5 second time constant and is applied only
to current harmonic measurements made when IEC mode is selected with SYSTem:CONF.
Command Syntax
CALCulate:SMOothing <Bool>
Parameters
0 | 1 | ON | OFF
*RST Value
OFF
Examples
CALC:SMO ON
Query Syntax
CALCulate:SMOothing?
Returned Parameters
<CRD>
Related Commands
MEAS:ARR:CURR:HARM? SYST:CONF
MEAS:CURR:HARM?