Instrument Subsystem
This subsystem programs the three-phase output capability of the Agilent 6834B .
Subsystem Syntax
INSTrument
:COUPle <phase> Couple all phases for programming (ALL | NONE)
:NSELect <n> Select the output phase to program (1 | 2 | 3)
:SELect <output> Select the output phase to program (OUTP1 | OUTP2 | OUTP3)
INSTrument:COUPle
Agilent 6834B Only
In a three-phase power source it is convenient to set parameters of all three output phases simultaneously
with one programming command. When INST:COUP ALL is programmed, sending a command to any
phase will result in that command being sent to all three phases.
NOTE: INSTrument:COUPle only affects the operation of subsequent commands. It does not by
itself immediately affect the ’s output. The commands that are affected by
INSTrument:COUPle are those with the designation: Phase Selectable.
INSTrument:COUPle has no affect on queries. There is no way to query more than one phase with a
single command. Directing queries to individual phases is done with INSTrument:NSELect.
Command Syntax
INSTrument:COUPle <phase>
Parameters
ALL | NONE
*RST Value
ALL
Examples
INST:COUP ALL
Query Syntax
INSTrument:COUPle?
Returned Parameters
<CRD>
Related Commands
INST:NSEL