Parameter Settings for Keypad Entry
Appendix B
B–6
Fine Tuning Functions
“B” Group Parameters Default Setting
User
Setting
Func.
Code
Name
-FE
(Europe)
-FU
(USA)
–FR
(Japan)
B_01 Selection of automatic restart
mode
00 00 00
B_02 Allowable under-voltage power
failure time
1.0 1.0 1.0
B_03 Retry wait time before motor
restart
1.0 1.0 1.0
B_12 Level of electronic thermal
setting
Rated
current for
each
inverter
Rated
current for
each
inverter
Rated
current for
each
inverter
B_13 Electronic thermal characteristic 01 01 00
B_21 Overload restriction operation
mode
01 01 01
B_22 Overload restriction setting Rated
current x
1.25
Rated
current x
1.25
Rated
current x
1.25
B_23 Deceleration rate at overload
restriction
1.0 1.0 1.0
B_31 Software lock mode selection 01 01 01
B_32 Reactive current setting Rated
current x
0.58
Rated
current x
0.58
Rated
current x
0.58
B_81 [FM] terminal analog meter
adjustment
80 80 80
B_82 Start frequency adjustment 0.5 0.5 0.5
B_83 Carrier frequency setting 5.0 5.0 12.0
B_84 Initialization mode (parameters
or trip history)
00 00 00
B_85 Country code for initialization 01 02 00
B_86 Frequency scaling conversion
factor
1.0 1.0 1.0
B_87 STOP key enable 00 00 00
B_88 Restart mode after FRS 00 00 00
B_89 Data select for digital op. OPE-J 01 01 01