Hitachi L100 Welding System User Manual


 
L100 Inverter
Configuring
Drive Parameters
3–9
“A” Group: Standard Functions
Basic Parameter Settings
These settings affect the most fundamental behavior of the inverter—the outputs to the
motor. The frequency of the inverter’s AC output determines the motor speed. You may
select from three different sources for the reference speed. During application develop-
ment you may prefer using the potentiometer, but you may switch to an external source
(control terminal setting) in the finished application, for example.
The base frequency and maximum frequency settings interact according to the graph
below (left). The inverter output operation follows the constant V/f curve until it reaches
the full-scale output voltage. This initial straight line is the constant-torque part of the
operating characteristic. The horizontal line over to the maximum frequency serves to let
the motor run faster, but at a reduced torque. If you want the motor to output constant
torque over its entire operating range (limited to the motor nameplate voltage and
frequency rating), then set the base frequency and maximum frequency equal as shown
(below right).
Base
Frequency
Maximum
Frequency
Base frequency =
maximum frequency
A03 A04
A03
A04
VV
100% 100%
ff
Constant torque
00
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
Units
A_01 Frequency source
setting
Three options; select codes:
00 ...Keypad potentiometer
01 ...Control terminal
02 ...Function F01 setting
01 01 00
F-SET-SELECT TRM
A_02 Run command source
setting
Two options; select codes:
01 ...Control terminal
02 ...Run key on keypad, or
digital operator
01 01 02
F/R SELECT TRM
A_03 Base frequency setting Settable from 50 Hz to the
maximum frequency
50.0 60.0 60.0 Hz
F-BASE 060Hz
A_04 Maximum frequency
setting
Settable from the base
frequency up to 360 Hz
50.0 60.0 60.0 Hz
F-MAX 060Hz