Hitachi L100 Welding System User Manual


 
“A” Group: Standard Functions
Configuring
Drive Parameters
3–16
Frequency-related Functions
Frequency Limits – Upper and lower
limits can be imposed on the inverter
output frequency. These limits will apply
regardless of the source of the speed refer-
ence. You can configure the lower
frequency limit to be greater than zero as
shown in the graph to the right. The upper
limit must not exceed the rating of the
motor or capability of the machinery.
Upper
limit
Frequency command
Lower
limit
Settable
range
A61
A62
Output
frequency
0
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
Units
A_61 Frequency upper limit
setting
Sets a limit on output
frequency less than the
maximum frequency (A_04)
Range is 0.5 to 360.0 Hz
0.0 ..setting is disabled
>0.1 setting is enabled
0.0 0.0 0.0 Hz
LIMIT H 000.0Hz
A_62 Frequency lower limit
setting
Sets a limit on output
frequency greater than zero
Range is 0.5 to 360.0 Hz
0.0 ..setting is disabled
>0.1 setting is enabled
0.0 0.0 0.0 Hz
LIMIT L 000.0Hz