Delta Electronics 230V Series Welder User Manual


 
Chapter 5 Parameters|VFD-S Series
Revision August 2006, SE08, SW V2.61 5-17
5.3 Description of Parameter Settings
Group 0: User Parameters This parameter can be set during operation.
0-00 Identity Code of the AC Motor Drive
Settings Read Only Factory setting: d#
0-01 Rated Current Display of the AC motor drive
Settings Read Only Factory setting: d ##.#
Pr. 0-00 displays the identity code of the AC motor drive. The capacity, rated current, rated
voltage and the max. carrier frequency relate to the identity code. Users can use the following
table to check how the rated current, rated voltage and max. carrier frequency of the AC
motor drive correspond to the identity code.
Pr. 0-01 displays the rated current of the AC motor drive. By reading this parameter the user
can check if the AC motor drive is correct.
115V/230V Series
KW 0.2 0.4 0.75 1.5 2.2
HP 0.25 0.5 1.0 2.0 3.0
Pr.0-00 d0 d2 d4 d6 d8
Rated Output Current (A) 1.6 2.5 4.2 7.5 11.0
Max. Carrier Frequency 10kHz
460V Series
KW 0.4 0.75 1.5 2.2
HP 0.5 1.0 2.0 3.0
Pr.0-00 d3 d5 d7 d9
Rated Output Current (A) 1.5 2.5 4.2 5.5
Max. Carrier Frequency 10kHz
0-02 Parameter Reset
Factory Setting: d0
Settings d9 All parameters are reset to factory settings (50Hz, 220V/380V)
d10 All parameters are reset to factory settings (60Hz, 220V/440V)
This setting allows the user to return all parameters to the factory default settings.
0-03
Start-up Display Selection
Factory Setting: d0
Settings d0 Display the frequency command value (LED F)
d1 Display the actual output frequency (LED H)
d2 Multifunction display, see Pr.0-04
d3 Display output current (LED A)