Delta Electronics 230V Series Welder User Manual


 
Chapter 5 Parameters|VFD-S Series
Revision August 2006, SE08, SW V2.61 5-41
GND
D7 Multi-step
1
D8 Multi-step 2
D9 Multi-step 3
Mx "Close": Operation available
Mx "Close": Operation available
Mx "Close": Operation available
These three inputs select the multi-step speeds defined by Pr.5-00 to Pr.5-06 as shown in the
following diagram. Pr.5-07 to Pr.5-16 can also control output speed by programming the AC drives
internal PLC function.
Freq.
Step 1
Step 2
Step 3
Step 4
Step 5
Step 6
Step 7
Time
OFF
ON
ON
ON ON
ON ON
ON ON
ON
ON ON ON
ON
Operation
Command
Mx3-GND
Mx2-GND
Mx1-GND
Pr.5-00
Pr.5-01
Pr.5-02
Pr.5-03
Pr.5-04
Pr.5-05
Pr.5-06
Master Freq.
d10 Jog Operation Control:
Parameter value d10 programs Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05), M3 (Pr.4-
06), M4 (Pr.4-07) or M5 (Pr.4-08) for Jog control.
GND
Mx "Close": Operation available
d10 jog operation
command
NOTE
Jog operation programmed by d10 can only be initiated while the motor is stopped. (Refer to Pr.1-13,
Pr.1-14.)
d11 Acceleration/Deceleration Speed Inhibit:
Parameter value d11 programs Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05), M3 (Pr.4-
06), M4 (Pr.4-07) or M5 (Pr.4-08) for Acceleration/deceleration Inhibit. When the command is
received, acceleration and deceleration is stopped and the AC drive maintains a constant speed.