Delta Electronics 230V Series Welder User Manual


 
Chapter 5 Parameters|VFD-S Series
5-24 Revision August 2006, SE08, SW V2.61
If the Upper Limit of Output Frequency is 50Hz and the Maximum Output Frequency is 60Hz,
the Maximum Output Frequency will be limited to 50Hz.
If the Lower Limit of Output Frequency is 10Hz, and the Minimum Output Frequency (Pr.1-05)
is set at 1.0Hz, then any Command Frequency between 1-10Hz will generate a 10Hz output
from the drive.
This parameter must be equal to or less than the Upper Limit of Output Frequency (Pr.1-07).
1-09 Acceleration Time 1 (Taccel 1) Unit: 0.1
1-10 Deceleration Time 1 (Tdecel 1) Unit: 0.1
1-11 Acceleration Time 2 (Taccel 2) Unit: 0.1
1-12 Deceleration Time 2 (Tdecel 2) Unit: 0.1
Settings d0.1 to d600Sec Factory Setting: d10.0
Pr.1-9- This parameter is used to determine the time required for the AC drive to ramp from 0
Hz to its Maximum Output Frequency (Pr.1-00). The rate is linear unless S-Curve is
“Enabled.”
Pr.1-10. This parameter is used to determine the time required for the AC drive to decelerate
from the Maximum Output Frequency (Pr.1-00) down to 0 Hz. The rate is linear unless S-
Curve is “Enabled.”
The acceleration/deceleration time 2 determines the time for the AC drive to
acceleration/deceleration from 0Hz to Maximum Output Frequency (Pr.1-00)
(acceleration/deceleration time 1 is the default). A Multi-Function Input terminal must be
programmed to select acceleration/deceleration time 2 and the terminals must be closed to
select acceleration/deceleration time 2. See Pr.4-04 to Pr.4-8-
In the diagram shown below, the acceleration/deceleration time of the AC drive is the time
between 0 Hz to Maximum Output Frequency (Pr.1-00). Suppose the Maximum Output
Frequency is 60 Hz, start-up frequency (Pr.1-05) is 1.0 Hz, and acceleration/deceleration time
is 10 seconds. The actual time for the AC drive to accelerate from start-up to 60 Hz is 9.83
seconds and the deceleration time is also 9.83 seconds.
1-13 Jog Acceleration/Deceleration Time Unit: 0.1Sec
Settings d0.1 to d600Sec Factory Setting: d10.0
1-14 Jog Frequency Unit: 0.1Hz
Settings d1.0 to d400Hz Factory Setting: d6.0