Chapter 5 Parameters|VFD-S Series
5-38 Revision August 2006, SE08, SW V2.61
Hz
0V
4mA
10V
20mA
30
0
60
Potentiometer Scale
Max.
Output
Freq.
60Hz
Pr.1-00
0Hz
0V
4mA
10V
20mA
Factory Settings
Pr.1-00=60Hz--Max. output Freq.
Pr.4-00=60Hz--Potentiometer bias freq.
Pr.4-01=1 -- bias polarity
Pr.4-02=100% -- pot. freq. gain
Pr.4-03=1 -- pot. REV. motion enable
anti-slope
4-04 Multi-function Input Terminal (M0, M1)
Settings d0 to d29 Factory Setting: d1
4-05 Multi-function Input Terminal (M2)
Factory Setting: d6
4-06 Multi-function Input Terminal (M3)
Factory Setting: d7
4-07 Multi-function Input Terminal (M4)
Factory Setting: d8
4-08 Multi-function Input Terminal (M5)
Factory Setting: d9
Parameters & Functions table:
Value Function Value Function
d0 No Function d15 Up: Increment master frequency
d1 M0: FWD / STOP, M1: REV / STOP d16 Down: Decrement master frequency
d2 M0: RUN / STOP, M1: FWD / REV d17 Run PLC Program
d3
3-Wire Operation Control mode (M0,
M1, M2)
d18 Pause PLC Program
d4 External Fault (Normally Open) d19 Counter Trigger Signal
d5 External Fault (Normally Closed) d20 Counter Reset
d6 External Reset d21
Select ACI / Deselect AVI (the priority is
higher than Pr. 2-00 and d26)
d7 Multi-Step Speed Command1 d22 PID function disable
d8 Multi-Step Speed Command2 d23 JOG FWD
d9 Multi-Step Speed Command3 d24 JOG REV
d10 Jog operation d25
The source of master frequency is AVI. (The
priority is higher than Pr. 2-00 and d26)
d11
Acceleration/Deceleration Speed
Inhibit
d26
The source of master frequency is ACI. (The
priority is higher than Pr. 2-00)
d12
First or Second Acceleration or
Deceleration Time Selection
d27
Press UP/DOWN
key to switch
forward/reverse (N.O.) motion
d13
External Base Block (N.O.)
(Normally Open Contact Input)
d28
Press UP/DOWN
key to switch
forward/reverse (N.C.) motion
d14
External Base Block (N.C.)
(Normally Close Contact Input)
d29
M0: 0: RUN 1: STOP, M1: no function,
Direction is controlled by keypad